Specifications:

Description:
Solid or stranded plain copper conductors, PVC insulated, laid up with bare copper earth wire, PVC sheathed overall.

Application:
For the wiring of:

Under-plaster wiring Roof wiring Under-floor wiring

Specification: SANS 1507/2002
Voltage Rating 300/500 V
Temperature Range -10°C to 70°C
Sheath colours Black and white
Core colours 2 core - black and red
3 core - blue, red and yellow
4 core - black, blue, red and yellow
 

Packaging:
Packaging 100 meter
Shrink-wrapped coils

Also available on 1000 meter Wooden drums


Technical Information

CABLE SIZE

#

CONDUCTOR
TYPE

NOMINAL
OVERALL
DIAMETER

CURRENT
RATING

NOTE 1

VOLT DROP


NOTE 1

APPROX. CABLE
WEIGHT
MASS PER
100M COIL

(mm2)

(MAIN)

(EARTH)

(mm)

(A)

(MV/A/M)

(kg)

1.0

1/1.5

1/1.5

7.9 x 4.3

15

44

6.76

1.5

1/1.38

1/1.15

8.8 x 4.8

19

29

8.33

2.5

1/1.78

1/1.38

10.4 x 5.6

27

18

11.7

4.0

7/0.86

1/1.38

12.2 x 6.2

36

11

18.3

6.0

7/1.04

1/1.78

13.7 x 7.2

46

7.3

23.4

10.0

7/1.38

7/0.86

17.2 x 8.6

63

4.4

37.1

16.0

7/1.72

7/1.04

20.0 x 9.8

85

2.8

52.0

 

Note 1: These ratings are for 2 cables single phase AC or DC clipped direct as per SANS 0142 table 6.3
# Conductors of 4mm2 and over are stranded


 



 
  Page last updated - 2009/05/09